YH5WZ-10KV Metal Oxide Lightning Arrester

Purpos

The Zinc Oxide lightning arrester is the most advanced over-voltage protector in the world. Because its core component resistors are made of Zinc Oxide and various metal oxides, compared with traditional silicon carbide arresters, it greatly improves the volt ampere characteristics of resistors, improves the capacity of resistors, and brings about the fundamental change of the characteristics of arresters.

When the lightning arrester under normal operating voltage, the current flow through the arrester only microamp level when subjected to voltage, non linear volt ampere characteristics of arrester excellent function, current flow through the arrester moment increased to several thousand amperes, lightning arrester in the conducting state, the release of piezoelectric energy, so as to effectively limit over against the voltage of power transmission equipment.

Use Condition

The temperature of the environment is not higher than +40 ℃, not less than -40 ℃.
The altitude is not more than 1000 (the plateau should be marked at the time of order).
The frequency of the power supply is not less than 48Hz, not more than 60Hz.
The power frequency voltage applied to the arrester for a long time does not exceed the continuous operating voltage of the arrester.
Maximum wind speed is not more than 35m/s;
The earthquake intensity is 7 degrees and below.
Mark the stain area.

Technical Performance

The performance of the products can meet the requirements of GB 11032-2000, JB/T8952-2005, JB/T10497-2005 and DL/T815-2002.

Model Description

Technical Parameter

ModelRated voltageSystem nominal voltageContinuous operating voltageDC (U1mA) reference voltageMaximum residual pressure KV (peak value)2000us square wave current (peak value)4/10us Impact current (peak value)0.75U1mA DC reference voltage
Maximum leakage current
Shock current of steep slopeLightning stroke currentOperating shock current
YH5WZ-12.7/4512.7106.62451.84538.31504050
YH5WZ-16.5/4516.51012.72451.84538.3
YH5WZ-17/45171013.62451.84538.3

Size

TNR-XK Combined multi function lightning protection socket

Technical parameter

ModelPower SupplynetworkTelephoneTV
Rated working voltage Un(V~)220/47-63Hz5V-48V-,110V-60V-
Maximum continuous operating voltage Uc(V~)3206.5V65V-,150V-80V-
Rated current I(A)10200mA200mA1A
Rated power P(kW)2.2///
Nominal discharge current In5kA3kA3kA5kA
Maximum discharge current lmax10kA///
Built-in thermal fuse120℃/10A///
Built-in self duplex overload protector16A///

TNR-XK Sketch map

TNR-A and TNR-G Surge protection power strip

Use and description

The TNR-B type is a leakage protection type, which can effectively prevent the occurrence of personal electric shock accidents and improve the safe operation of the equipment.

The TNR-G type lightning protection socket is installed in the 19 inch standard cabinet. It can be used as an equipment’s surge protection device, so that the device is free from transient or overvoltage damage caused by lightning or electronic interference. It can be widely used in office, machine room and industrial place. It is especially suitable for industrial and electronic cabinet, including PC cabinet, data frame, network cabinet and industrial control cabinet. It provides a perfect protection for the AC power supply of sensitive equipment.

 For the reliable protection of precision equipment for you, please strictly install wiring (L- logo red, N- black, PE- color), the ground wire should be connected by 4mm – Multi Strand copper wire.

Technical parameter

ModelTNR-ATNR-B(Leakage protection type)TNR-G
Rated working voltage Un(V~)220/47-63Hz220/47-63Hz
Maximum continuous operating voltage Uc(V~)320320
Rated current I(A)1016
Rated power P(kW)2.23.5
Nominal discharge current In5kA5kA
Maximum discharge current lmax10kA10kA
Built-in thermal fuse120℃/10A120℃/16A
Built-in self duplex overload protector16A20A

Product size diagram

TNR-RS lightning surge protecto

Installation and maintenance

1. this product is connected to the input terminal of the protected equipment.

2. from the terminal to the grounding end grounding, to ensure good grounding, grounding wire distance grounding bus should not be too long, kept within 0.5 meters.

3. if the thunderstorm day after, the signal can not be transmitted normally, after pulling down this product, re connected after the normal transmission of the signal, indicating that the product has been damaged.

Technical parameter

ModelTNR-RS232/9TNR-RS232/25TNR-RS485/4
Number of protective needles9254
Shape size(mm)25×35×2977×55×2975×36×25
Protective footAll pins2,3,4,5,6,8,20,221,2,3,4
Rated working voltage Un(V-)1512
Maximum continuous operating voltage Uc(V-)2515
Nominal discharge current In(KA)0.25
Transmission frequency MHz210
Insertion loss dB<0.5<0.5
Protection modeLine – line  line-landLine – line  line-land

Product connection

TNR-SV Combined inline surge protector

Installation matters

     The system incoming line is connected to the input end of the lightning protection device, then the lead line from the lightning protection device is received from the protected equipment, and the ground leads from the earthing end to ensure good grounding.

Technical parameter

Model specification / parameterTNR-SV/3TNR-SV/2TNR-SV/W IP Camera
Power SupplyvideocontrolPower SupplyvideoPower SupplyNetwork (support POE)
working voltage Un220V~ 24~24V- 12V6V- 12V-220V~ 24~24V- 12V6V- 12V-220V~ 24~24V- 12V5V-
Nominal discharge current In5-10kA5kA5-10kA5kA5-10kA3kA
Maximum discharge current lmax10-20kA/10-20kA/10-20kA/
Transmission frequency/20M,10M/20M/100M,1000M
Nominal flow rate1A200mA1A200mA1A200mA
insertion loss/<0.5dB/<0.5dB/Isolated protection
Outer size120×68×30 mm

Product connection

TNR-T Video lan surge protector

The coaxial lightning arrester adopts two stage surge protection. First stage discharge lightning current, second stage overvoltage. In the specified transmission frequency range, by properly protecting device parameters, the most of the energy of the overvoltage is released at the first stage, and the residual voltage is further clamped at level second, and the protection level is controlled within the safety voltage of the device.

TNR-BNC series multi interface signal lightning arrester, using standard 19 inch cabinet design, easy to install and maintain.

Technical parameter

ModelTNR-T/BNCTNR-T/BNC Multi interface
Rated working voltage Un(V-)6
Maximum continuous operating voltage Un(V-)7.2
Nominal discharge current In(kA)5
Transmission frequency (MHz)30
insertion loss (dB)<0.5
Joint formBNC-KK、BNC-KJ
work environmenttemperature -40~+70℃ ,relative humidity≤95% (25℃)

Product installation wiring diagram

TNR-K Coaxial antenna network surge protector

TNR-K series antenna signal lightning protection is the antenna system, including satellite antenna, microwave, mobile communication, intercom system antenna and radar antenna etc.

ModelTNR-K/BNCTNR-K/FTNR-K/SMATNR-K/N
Working frequency range0~2.0G0~1.0G0~1.0G0~2.0G
Common impedance50Ω75Ω75Ω50Ω
Nominal ignition voltage75~100V
Maximum discharge current5kA
Limited voltage10kA
Voltage in Bobbi≤550V
insertion loss≤1.2dB
Joint formK/K、K/J、J/J
work environmenttemperature -40~+70℃
Shape sizeabout 60×25×25mm

Product connection

TNR-RJ Network signal lightning arrester

Working principle

TNR-RJ series signal lightning arrester circuit adopts two level protection, before most of the energy transfer overvoltage, discharge lightning current, a voltage clamp on the level, voltage level and the residual pressure is lower than the two level of electronic equipment, the precise decoupling device with strong will, play a good protective effect.

Installation matters

The TNR-RJ series lightning protector is connected in series between the protected device and the transmission cable. The input port (IN) is connected to the signal channel, and the output terminal (OUT) is connected with the protected device. The multi strand copper core wire connects the earthing end of the signal lightning arrester with the adjacent ground confluence.

Technical parameter

ModelRated working voltage Un(V-)Maximum continuous operating voltage Uc(V-)Nominal discharge current In(kA)Transmission frequency MHzinsertion loss dBInterfaceProtective foot
TNR-RJ12/48-2(RJ11)486532<0.5RJ123,4
TNR-RJ12/48-4(RJ11)486532<0.5RJ123,4and2,5
TNR-RJ12/110-2(RJ11)11015032<0.5RJ123,4
TNR-RJ12/110-4(RJ11)11015032<0.5RJ123,4and2,5
TNR-RJ12/180-2(RJ11)18024032<0.5RJ123,4
TNR-RJ12/180-4(RJ11)18024032<0.5RJ123,4and2,5
TNR-RJ45/05-4056.53100<0.5RJ451,2,3,6
TNR-RJ45/05-8056.531000<0.5RJ451,2/3,6/4,5/7,8
TNR-RJ45/POEsignal056.53100<0.5RJ451,2,3,6
Power Supply48655/ RJ454,5and7,8

TNR Lightning protection grounding system

Adaptation range

The grounding bar shows:

The TNR- grounding rod is made of copper clad steel and zinc coated steel, which can effectively prevent the corrosion of the steel bar. Users can choose the same type of Baotou Steel, copper thickness and grounding electrode according to the environmental geology.

Technical parameters of grounding rod

ModelTexture of materialSizeThickness of copper / zinc layer  mmProductive length  m
Grounding rodCopper clad steelφ 14,15,18,20,22,24,420.25,0.3,0.5,1.01-6
Grounding rodZinc clad steelφ 14,15,18,20,22,24,421.01-6

YH10W-110KV Surge Arrester In Substation

Use characteristics

  The Zinc Oxide lightning arrester is the most advanced over-voltage protector in the world. Because its core component resistors are made of Zinc Oxide and various metal oxides, compared with traditional silicon carbide arresters, it greatly improves the volt ampere characteristics of resistors, improves the capacity of resistors, and brings about the fundamental change of the characteristics of arresters.

     When the lightning arrester under normal operating voltage, the current flow through the arrester only microamp level when subjected to voltage, non linear volt ampere characteristics of arrester excellent function, current flow through the arrester moment increased to several thousand amperes, lightning arrester in the conducting state, the release of piezoelectric energy, so as to effectively limit over against the voltage of power transmission equipment.

Conditions of use

The temperature of the environment is not higher than +40℃, not less than -40℃
The altitude is not more than 1000 (the plateau should be marked at the time of order).
The frequency of the power supply is not less than 48Hz, not more than 60Hz.
The power frequency voltage applied to the arrester for a long time does not exceed the continuous operating voltage of the arrester.
The maximum wind speed is not more than 35m/s;
The earthquake intensity is 7 degrees and below.
Mark the stain area.
 

Technical performance

The performance of the products can meet the requirements of GB 11032-2000, JB/T8952-2005, JB/T10497-2005 and DL/T815-2002.

Model description

technical parameter

ModelRated voltageSystem nominal voltageContinuous operating voltageDC (U1mA) reference voltageMaximum residual pressure KV (peak value)2000us square wave current (peak value)4/10us impact current (peak value)0.75U1mA DC reference voltage
Maximum leakage current
Shock current of steep slopeLightning stroke currentOperating shock current
YH10WZ-100/2601001107814529126022160010050
YH10WZ-102/2261021107906148291266226
YH10WZ-108/28110811084157315281239

Shape size

Chinese Suppliers Surge Protection Device OEM SPD DC Surge Protector

Characteristic

1. flashover precision

2. wide range of protection

3. passivity, no radioactivity, no interference

4. reducing counterattack and lightning induced overvoltage

5. non corrosion, maintenance free, strong resistance to wind

6. easy to install and beautiful in shape

TNR-CB

ModelFlange height MTexture of materialworking temperature
TNR-CB1.2Stainless steel-40~+80℃
1.5
1.8
The maximum can be done 20 meters

Product mix

YH5W-35KV Arrester Electrical

Basic Principle

     When the lightning arrester under normal operating voltage, the current flow through the arrester only microamp level when subjected to voltage, non linear volt ampere characteristics of arrester excellent function, current flow through the arrester moment increased to several thousand amperes, lightning arrester in the conducting state, the release of piezoelectric energy, so as to effectively limit over against the voltage of power transmission equipment.

Use characteristics

The electrical equipment used by the Zinc Oxide lightning arrester to protect the AC power system is protected from overvoltage and overvoltage damage.

Conditions of use

The temperature of the environment is not higher than +40 C, not less than -40 C
The altitude is not more than 1000 (the plateau should be marked at the time of order).
The frequency of the power supply is not less than 48Hz, not more than 60Hz.
The power frequency voltage applied to the arrester for a long time does not exceed the continuous operating voltage of the arrester.
The maximum wind speed is not more than 35m/s;
The earthquake intensity is 7 degrees and below.
Mark the stain area.
 

Technical performance

The performance of the products can meet the requirements of GB 11032-2000, JB/T8952-2005, JB/T10497-2005 and DL/T815-2002.

Model description

Technical parameter

ModelRated voltageSystem nominal voltageContinuous operating voltageDC (U1mA) reference voltageMaximum residual pressure KV (peak value)Operating shock current4/10us impact current (peak value)0.75U1mA DC reference voltage
Maximum leakage current
Shock current of steep slopeLightning stroke currentOperating shock current
YH5WZ-42/134423523731541341144006550
YH5WZ-51/134513540.873154134114
YH5WZ-52.7/13452.73540.873154134114
YH5WZ-54/13454354173154134114

Shape size